Description
Features & Benefits
5-Year Battery Powered; 6 Digit Display – Floating Decimal; Batch & Cumulative Totals; Factory Calibrated and Field Calibratable; Add-On Output Options; FM Approved Class I, Div. I, Groups A-G; Choice of Gallons or Liters
Applications
Gasoline (up to 15% alcohol blends such as E15), Diesel Fuel (up to 20% biodiesel blends such as B20), Biodiesel (B100) and Kerosene.
Application Notes
Unidirectional but Display can be rotated 180°, Can mount Horizontally or Vertically, Can use for Gravity Feeds, Line must be full (no air) for proper accuracy, No Rate of Flow (For Rate & Total see A109GMA200NA2)
Flow Specifications
- Accuracy (% of Reading) Factory Calibrated with Computer: ± 1.5%
- Repeatability (based on test conditions): ± 0.2%
- Pressure Rating: 300 PSI (21 Bar)
- Operating Temp With Local Computer: 14°F to 140°F (-10°C to 60°C)
- Operating Temp Without Local Computer or With Remote Computer: -40 to 250°F (-40 to 121°C) [Opt’l]
- Max Pressure Drop (at Max Flow in test conditions): 7 PSI
- Maximum Viscosity: 100 cps**
- Recommended Strainer Size: 35 Mesh (500 Microns)
- Max. Particle Size: .018″ / .457 mm
Wetted Materials
- Housing Material: Aluminum
- Rotor: Nylon
- Bearings: Ceramic
- Shaft: Tungsten Carbide
- Signal Generator: Ferrite
- Retaining Rings: 316SS
- Seals: n/a
General Information
- Design: Fuel Meter – Aluminum (300 PSI)
- Std Calibration Reports Included: No
- Local Computer Calibrations: Factory Only
- Warranty Period: 1 Year
- Approvals Notes: See catalog page for full approval specs
- Comments: This is a totalizing meter only. It does not display rate of flow.
- Comments: **For viscous fluids like oils, the temperature must not fluctuate more than ±5°F to avoid accuracy fluctuations
Meter Display & Output Signal
- Display Type: Digital LCD
- Local/Remote Display: Local
- Display Function: 1 Cumulative, 1 Batch
- LCD Digits: 6
- Totalizing Display Starting Increment: 0.01
- Totalizing Resets to 0 After Reaching: 99,999,999
- Remote Output: None
Electronics
- Sensor (Pickup): Magnetic
- Battery Power: (2) 3V Lithium Battery (5 year)
Piping Requirements
- Desired Straight Pipe Dia.s: 40″ Upstream / 10″ Downstream
- Minimum Straight Pipe Dia.s: 40″ Upstream / 10″ Downstream
Weight & Dimensions
- Connection to Connection Length (OAL): 6.0″ (152 mm)
- Shipping Weight (Approximate): 4.2 lbs (1.9kg)